loading

Is specialized in designing, manufacturing for power transformers ,furnace transformers and reactor.

63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 1
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 2
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 3
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 4
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 5
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 6
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 7
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 1
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 2
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 3
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 4
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 5
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 6
63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation 7

63000kVA 110kv Explosion-Proof Electric Power Transformer/Power Transformer Substation

Basic Info.

Model NO.
S (FSZ) 11
Usage
Power Transformer, Distribution Transformer
Frequency Characteristics
High Frequency
Shape of Core
OD
Brand
Ville
Rated Voltage
110kv
Standard
IEC Standard
Connection
Ynyn
Rated Power
63000kVA
Transport Package
wooden case or as per requirement
Specification
According to specification
 
Origin
China
HS Code
85
Production Capacity
50,000 set/year

Product Description

Explosion-proof electric power transformer/power transformer substation
Technical parameters:
6300-63000/110 series three phase non-magnetization regulating transformer
Ratedpower
(kVA)
Valtage Connction 9 loss(kW) 10 loss(kW) 11 loss(kW) No-load Loss
(%)
Impedence Voltage
(%)
Weight(t) Outline Dimension(mm) Guage
(mm)
H.V
(kV)
M.V
(kV)
L.V
(kV)
No-Load Loss Load Loss No-Load Loss Load Loss No-Load Loss Load Loss Oil weight Untanking
weight
Total weight L B H
6300 110
121
±2
×2.5%
35
38.5
6.3
6.6
10.5
11
YNyn
0d11
11.2 47 10.1 44.7 9 44.7 0.82 step up
H-M:
17-18
H-L:
10.5
M-L:
6.5
step-down
H-M:
10.5
H-L:
17-18
M-L:
6.5
6 17 20 5400 2900 4300 1475
8000 13.3 56 12.0 53.2 10.6 53.2 0.78 7 20 24 5500 3100 4400 1475
10000 15.8 66 14.2 62.7 12.6 62.7 0.74 8 23.5 27 5600 3300 4450 1475
12500 18.4 78 16.6 74.1 14.7 74.1 0.70 8.5 25 30 5900 3350 4500 2040
16000 22.4 95 20.2 90.3 17.9 90.3 0.66 8.8 27 32 6000 3400 4550 2040
20000 26.4 112 23.8 106.4 21.1 106.4 0.65 9 30.5 33 6050 3450 4600 2040
25000 30.8 133 27.7 126.4 24.6 126.4 0.60 9.2 34 36 6100 3500 4650 2040
31500 36.8 157 33.1 149.2 29.4 149.2 0.60 9.5 37.5 46 6150 3550 4700 2040
40000 43.6 189 39.2 179.6 34.9 179.6 0.55 10.5 44 56 6200 3600 4750 2040
50000 52.0 225 46.8 213.8 41.6 213.8 0.55 15.5 55 73 6500 4200 5000 2040
63000 61.6 270 55.4 256.5 49.3 256.5 0.50 20 65 81 6800 4400 5100 2040