This tap changer is mainly used for combined type (base type) transformer,which is called as “American-box type”in our country. It must tap and change under off-circuit status, and is used to finish voltage regulating function of primary coil.
American-BOX TYPE CAGE OFF-CIRCUIT TAP SWITCH- Used in mineral oil or silicon oil
- Rated Voltage 10KV-36KV
- Rated current from 63A-125A
- Tapping position: 3-5
- Regulation 2.5% per position
Model Explanation
WST □ - □/□-□X□
W: off-circuit
S : three-phase or D for single phase
T : linear type tap changer
□: voltage regulation model
□: rated current
□: rated voltage
□: number of tapping heads
□: number of tapping position
Voltage Regulation Model
I : terminal point
II : central point
III : neutral point
IV : Y-△ conversion
V : series-parallel connection
Our Advantage
* High pressure capability
* Strong anti-aging ability
* Strong anti-lightning impact
* Strong protection
* Use smoothly
* Stable use
Model No. | Rated voltage kV |
Installation dimension (mm) |
|||
H1 | H2 | H | Md | ||
WSLII263~125/10-4×3 | 10 | 95 | 65 | 245 | 63A,Md=M6;125A,Md=M8 |
WSLⅡ263~125/10-6×5 | 95 | 65 | 245 | ||
WSLⅡ263~125/20-4×3 | 20 | 110 | 100 | 330 | |
WSLⅡ263~125/20-6×5 | 110 | 100 | 330 | ||
WSLⅡ263~125/35-4×3 | 35 | 130 | 110 | 370 | |
WSLⅡ263~125/35-6×5 | 130 | 110 | 370 |
Model No. | Rated voltage kV |
Installation dimension (mm) |
|||
H1 | H2 | H | Md | ||
WSLⅡ363~125/10-4×3 | 10 | 105 | 65 | 255 | 63A,Md=M6;125A,Md=M8 |
WSLⅡ363~125/10-6×5 | 105 | 65 | 255 | ||
WSLⅡ363~125/20-4×3 | 20 | 120 | 100 | 345 | |
WSLⅡ363~125/20-6×5 | 120 | 100 | 345 | ||
WSLⅡ363~125/35-4×3 | 35 | 135 | 110 | 380 | |
WSLⅡ363~125/35-6×5 | 135 | 110 | 380 |