Product Description
Introduction to Structure
Voltage transformer matched with GIS is used for SF6 close combined apparatus; it is connected between the
phase and ground. It uses SF6 gas as main insulation, and uses polyester film, which is used for interlayer
insulation, as additional insulation.
Main components of transformer
There are lifting blocks, a ground terminal, a nameplate, an instruction plate and a secondary terminal box on
the metal shell. The shell body is formed by welding steel plates and hot galvanizing, all connecting bolts uses
stainless standard parts, they can work in outdoor place for long time, and do not rust forever. A metal rupture
disc is installed on the base. If a high energy discharge occurs in it, the rupture disc will break to relief pressure,
so the safety of product is improved.
Main body is installed in the shell, high voltage electrode and low voltage shielded plate use aluminum plates,
which are rotated and pressed to form and carried out polishing treatment. Optimal Electrode shielded structure
improves internal and external field distribution of the product. It has an excellent insulation property. Partial
discharge test is carried out under power frequency test voltage.
High voltage coil uses single-staged tower structure, so it has a good shock resistant performance. Use
imported polyester films and high strength enameled wires, so it has high insulation strength. Use imported
automatic winding equipment to complete the wire winding and the wrapping of interlayer insulation
automatically according to entered instructions.
It can be designed and made with three coils (one primary coil, one secondary coil and one residual voltage
coil) or four coils (one primary coil, two secondary coils and one residual voltage coil) according to the
requirement of customer.
Disc insulator is used as the partition between the gas chamber of transformer and that of composite apparatus.
Transformer and composite apparatus can have SF6 gas with different pressure. The connection between high
voltage conductor and high voltage electrode on main body uses elastic structure.
Leading wire of secondary coil and leading wire of ground terminal of primary coil are connected with Phoenix
special terminal in the secondary terminal box via the terminal block cast as a whole with epoxy on the shell. It is
more convenient for operations such as plug-in, pull-out and wiring etc. The sealing performance meets the
requirement of IP55.
The transformer can be installed horizontally or vertically.