No. | Name | Unit | Parameter | ||
1 | Rated voltage | kV | 12 | ||
2 | Rated current | A | 5~3150 | ||
3 | Main busbar rated current | A | 630, 1000 | 1000,2000 | 2500,3150 |
4 | Rated short-circuit breaking current | kA | 20 | 31.5 | 40 |
5 | Rated short-time withstand current | kA | 20 | 31.5 | 40 |
6 | Rated peak withstand current | kA | 50 | 80 | 100 |
7 | Rated short-circuit making current (peak) | kA | 50 | 80 | 100 |
8 | Hot stable time | s | 4 | ||
9 | Degrees of protection | IP2X | |||
10 | Busbar system | Single busbar, Bibusbar Single busbar with bypass |
|||
11 | Operation mode | Electromagnetic type, spring energy storage type | |||
12 | Dimensions (Width×Depth×Height) | mm | 1100×1200×2650 | 1200×1300×2650 | |
13 | Net Weight | kg | 400 | 500 | |
14 | Packing Dimensions (Width×Depth×Height) | mm | 1260×1700×2920 | 1360×1800×2920 | |
15 | Gross weight | kg | 500 | 600 |